REVISION IN IS 1180: HIGHLIGHTED POINTS (PART II)
Recently Bureau of Indian Standards issued the
Fourth revision of IS 1180 (Part 1): Outdoor Type Oil Immersed Distribution
Transformers upto 2500 kVA, 33KV Specification. To discuss the various changes in
design parameters of IS we had arranged a technical session in our office on
dtd. 20.09.2014.
This session was headed by Mr. Arun Kumar (VP)
having the vast experience in electrical & mechanical designing of
transformer and previously he had served in BHEL, Haridwar as a design Head,
Mr. Sandeep Kumar (AGM Design) & Mr. Gaurav Jain (Sr. Manager Marketing)
have also attended the technical session to discuss the technical parameters
which are defined in revised IS 1180. Our MD Mr. Girish Kumar also attended the
technical session and also gives their valuable inputs in technical session.
In this technical session we have discussed the
different categories in which transformers have been divided, which are as
below.In revised IS 1180 there are three energy efficiency levels and for each
categories, maximum values of total losses have been defined on 50% load and
100% load. Losses & percentage value of impedance for different categories
are as below:
a)
Three phase distribution transformers upto and including 200 KVA, 11KV Class
Sl. No.
|
Rating (KVA)
|
% Z
|
Energy Efficiency
Level 1
|
Energy Efficiency
Level 2
|
Energy Efficiency
Level 3
|
|||
@ 50%
|
@ 100%
|
@ 50%
|
@ 100%
|
@ 50%
|
@ 100%
|
|||
1
|
16 KVA
|
4.5%
|
150W
|
480W
|
135W
|
440W
|
120W
|
400W
|
2
|
25 KVA
|
4.5%
|
210W
|
695W
|
190W
|
635W
|
175W
|
595W
|
3
|
63 KVA
|
4.5%
|
380W
|
1250W
|
340W
|
1140W
|
300W
|
1050W
|
4
|
100 KVA
|
4.5%
|
520W
|
1800W
|
475W
|
1650W
|
435W
|
1500W
|
5
|
160KVA
|
4.5%
|
770W
|
2200W
|
670W
|
1950W
|
570W
|
1700W
|
6
|
200KVA
|
4.5%
|
890W
|
2700W
|
780W
|
2300W
|
670W
|
2100W
|
b)
Three phase distribution transformers Higher than 200 KVA upto and including
2500 KVA, 11KV Class
Sl. No.
|
Rating (KVA)
|
% Z
|
Energy Efficiency
Level 1
|
Energy Efficiency
Level 2
|
Energy Efficiency
Level 3
|
|||
@ 50%
|
@ 100%
|
@ 50%
|
@ 100%
|
@ 50%
|
@ 100%
|
|||
1
|
250 KVA
|
4.5%
|
1050W
|
3150W
|
980W
|
2930W
|
920W
|
2700W
|
2
|
315 KVA
|
4.5%
|
1100W
|
3275W
|
1025W
|
3100W
|
955W
|
2750W
|
3
|
400 KVA
|
4.5%
|
1300W
|
3875W
|
1225W
|
3450W
|
1150W
|
3330 W
|
4
|
500 KVA
|
4.5%
|
1600W
|
4750W
|
1510W
|
4300W
|
1430W
|
4100W
|
5
|
630 KVA
|
4.5%
|
2000W
|
5855W
|
1860W
|
5300W
|
1745 W
|
4850W
|
6
|
1000 KVA
|
5.0%
|
3000W
|
9000W
|
2790W
|
7700W
|
2620W
|
7000W
|
7
|
1250 KVA
|
5.0%
|
3600W
|
10750W
|
3300W
|
9200W
|
3220W
|
8400W
|
8
|
1600 KVA
|
6.25%
|
4500W
|
13500W
|
4200W
|
11800W
|
3970W
|
11300W
|
9
|
2000 KVA
|
6.25%
|
5400W
|
17000W
|
5050W
|
15000W
|
4790W
|
14100W
|
10
|
2500 KVA
|
6.25%
|
6500W
|
20000W
|
6150W
|
18500W
|
5900W
|
17500 W
|
c)
Single Phase distribution transformers upto and including 25 KVA, 11KV Class
Sl. No.
|
Rating (KVA)
|
% Z
|
Energy Efficiency
Level 1
|
Energy Efficiency
Level 2
|
Energy Efficiency
Level 3
|
|||
@ 50%
|
@ 100%
|
@ 50%
|
@ 100%
|
@ 50%
|
@ 100%
|
|||
1
|
5KVA
|
4.0%
|
40W
|
115W
|
35W
|
95W
|
30W
|
75W
|
2
|
10KVA
|
4.0%
|
70W
|
190W
|
60W
|
170W
|
55W
|
150W
|
3
|
16KVA
|
4.0%
|
95W
|
265W
|
82W
|
224W
|
63W
|
190W
|
4
|
25KVA
|
4.0%
|
125W
|
340W
|
110W
|
300W
|
95W
|
260W
|
After study of the above we observe followings
points which are important for design of transformers:
1) Mr. Sandeep pointed out that losses of energy
efficiency level 1 are equivalent to BEE 3 Star Category, energy efficiency
level 2 are equivalent to BEE 4 star category and energy efficiency level 3 are
equivalent to 5star category for 3 phase distribution transformer upto 200 KVA
transformer for 11KV Class.
2) Mr. Gaurav Jain pointed out that losses in energy
efficiency level 1 are less than the losses mentioned in ECBC 2009 for
transformers higher than 200 KVA upto and including 2500 KVA for 11KV Class
Further to above our design head also observed that
IS 1180 are now also applicable for 22KV & 33KV class transformers, losses
values for 22KV & 33KV class transformers shall be applicable as per below
clause:
a) For transformers having voltage class above 11KV
and upto and including 22KV, the permissible total loss value shall not exceed
by 5% of the maximum total losses values mentioned in table b) for 3 phase.
b) For
transformers having voltage class above 22KV and upto and including 33KV, the
permissible total loss value shall not exceed by 7.5% of the maximum total
losses values mentioned in table b) for 3 phase.
c) For transformers having voltage class above 11KV
and upto and including 22KV, the permissible total loss value shall not exceed
by 7.5% of the maximum total losses values mentioned in table c) for single
phase.
d) For transformers having voltage class above 22KV
and upto and including 33KV, the permissible total loss value shall not exceed
by 5% of the maximum total losses values mentioned in table c) for single
phase.
In revised IS 1180 there are also some change in oil
& winding temperature rise parameters for each category. It also includes
the specification for corrugated type transformers. Since our MD Mr. Girish
Kumar & our Organization is always emphasize & committed to saving the
energy, so we appreciate the BIS & Government of India for taking this step.
It will be a great tool for us to serve the nation by saving energy. SAI
Electricals already has models HEFF for Level 1 and shortly will come up with
models of transformers for Level 2 & Level 3.